Skip to content
LEVENT MARINE
Back to services
Autronica · Consilium · Notifier

Fire Alarm & Detection

Loop faults, false alarms, detector head sensitivity, CO2/HI-FOG release matrix, PA/GA STI. SOLAS Ch. II-2 ready.

Service available at all US ports — 24/7 worldwide. Our next available technician contacts you within 1 hour.

Fire Alarm & Detection
Symptom checklist

What we hear from the bridge.

  • Autronica BS-100 zone fault, loop current outside 18–22 mA
  • Consilium Salwico CS3000 false alarms in galley
  • PA/GA STI below 0.5 in engine room (IEC 60849)
  • CO2 release pilot solenoid fails 24VDC continuity
  • Detector head sensitivity out of tolerance per maker chart
  • Loop short-to-earth after recent welding
Likely root causes

Where the fault usually lives.

  • Loop shield discontinuity after hot work in cargo hold
  • Detector head soot loading beyond chamber threshold
  • Loudspeaker line short-to-ground after deck wash ingress
  • Pilot CO2 cylinder pressure below 50 bar
Equipment we bring

Calibrated test equipment, class-acceptable reports.

  • Autronica AutroMaster service laptop & loop analyser
  • Consilium SW3000 service tool
  • B&K 2270 sound level analyser with STI/STIPA module
  • Solo 330 functional smoke/heat tester pole
  • Cal gas: CH4 50% LEL, H2S 10 ppm, CO 100 ppm

Reports compatible with DNV · BV · ABS · Lloyd's · TL · RINA · ClassNK · IRS.

Often needed together

Parts most often requested with this service.

  • fire detectors
  • co2 solenoids
  • pa ga amps
  • loop cable
FAQ

Common questions for this system.

Which fire panel makers do we service?
Autronica BS-100 and AutroSafe IFG, Consilium Salwico CS3000 and CS4000, Notifier marine, Tyco Marioff (where the loop architecture applies), Minimax (passenger ships). Service tools for the first three on every dispatch.
How long does a typical false-alarm attendance take?
Three to six hours from boarding to class report. Contamination cases run longer (every head in the suspect zone and adjacent zones gets tested). Loop earth faults are typically shorter.
Can we cover SOLAS Ch.II-2 annual survey at the same attendance?
Yes. We coordinate the annual fire-detection survey with the root-cause attendance and produce a single combined class report. Surveyors prefer this — one visit, one signature, fewer port days lost.

Have a vessel calling?

Three quick questions — port, when, contact. Our next available technician will contact you within 1 hour.