Skip to content
LEVENT MARINE
Class & survey

Special Survey Electrical Prep: 10-Point Walk-Through for Bulkers and Tankers

13 min readCompliance & Class

What the surveyor walks with on day one of a 5-year Special Survey — ACB primary injection, insulation resistance trends across the 440V distribution, bus-tie discrimination on paper, emergency switchboard blackout drill, and the class-template paperwork that closes the visit in days instead of weeks.

Why Special Survey writes more electrical findings than any other class event

A 5-year Special Survey carries roughly four times the writable-deficiency rate of an Annual Survey across the same vessel category. The reason is not that the equipment failed in year five — it is that the documentation gap from five years of incremental change has accumulated. Every Annual Survey patched the small things. The Special Survey asks the question nobody asks at the Annual: does the as-fitted electrical installation still match the as-classed drawings, and is each protection device set to a value that the discrimination calculation still supports?

We attend Special Survey preparation on bulkers, product tankers, container ships and offshore support vessels at all major US ports. The walk-through below is the version we run with the chief engineer's electrical team approximately three months before the surveyor boards. It is not a substitute for the class society's checklist — it is a working ETO's pre-pass, designed to clear the most common findings before they are written up.

1. Switchboard ACB primary injection — schedule it, do not surprise it

Every Air Circuit Breaker (ACB) on the main switchboard, the emergency switchboard and any 690V or 6.6kV substation needs a primary injection test against its nameplate trip curve at the 5-year Special. The test is not optional. Vessels that go through five years without an injection record on the ACBs will be required to do them under the surveyor's clock — which means a stripped switchboard during the survey, which means the survey closes in weeks rather than days.

Run primary injection with a SVERKER 900 or equivalent (3000A capability for typical marine ACBs, 5000A if the installation includes large bus-tie breakers). Capture long-time pickup, short-time pickup, instantaneous pickup, and ground-fault pickup if fitted. Compare each against the nameplate ±10% per IEC 60947-2. ACBs that drift outside that band need the trip unit replaced — the unit, not the entire breaker.

2. Insulation resistance trend across the 440V distribution

Single insulation readings from the Special Survey week mean nothing. What the surveyor expects is a trend across the survey cycle — typically four to five readings spaced six months apart for each major feeder. A trend that is flat or rising is a healthy installation. A trend that is sloping down 10–15% per year is a feeder approaching the IEEE 43 recommended minimum, and the surveyor will flag it as a watch item even if the current value is technically passing.

Audit the engine room insulation log. If readings are missing for periods longer than nine months, take three new readings now (using a Megger MIT525 at 1kV with PI/DAR on motors, 500V for general distribution) and add them to the log with the operating context — wet bilge, dry season, motor recently cleaned. Surveyors accept a documented gap with explanation; they do not accept a blank period.

3. Bus-tie discrimination — surveyors check the trip-curve overlap on paper

Discrimination between an upstream ACB and a downstream feeder breaker is a paper calculation supported by the trip-curve overlap in the protection coordination study. The Special Survey asks for the coordination study; vessels that produce a study from the original shipyard are routinely flagged if any breakers have been replaced or any settings have been changed since. The study has to reflect the as-fitted installation, not the as-built one.

Rebuild the coordination study before the survey if any ACB trip unit, MCCB or MCB has been replaced, re-rated or re-set in the past 5 years. We carry parametric coordination tools (ETAP, SKM PowerTools) and can rebuild the study in a working day for a typical mid-size vessel. The output is a one-page coordination diagram per bus, time-current curves overlaid, and a written conclusion the surveyor signs against.

4. Emergency switchboard load test — actual blackout drill, not document

SOLAS II-1 Reg.43 requires the emergency generator to auto-start within 45 seconds of a main-bus blackout and to take the emergency switchboard load to full rating within an additional 15 seconds. The Annual Survey accepts a witnessed start-test on the dock; the Special Survey asks for the full blackout drill — main breaker open, lights out, emergency genset cranks, breaker closes, ER lighting recovers, steering gear recovers, fire pump auto-starts.

Schedule the drill at anchor or during a quiet alongside watch. The fuel oil purifiers and the boiler can be excluded by isolation; the steering gear, the fire pump, the bridge navigation and the radio installation cannot. If the emergency genset cannot take all four within 60 seconds total, you have a writable observation. We carry a stop-watch capture device that timestamps the breaker state changes to a class-witnessed log.

5. Fire detection loop integrity + sensitivity calibration certificates

The fire detection loop is checked at every Annual; the Special Survey adds a sensitivity audit. Every detector head should have a sensitivity certificate within the past calendar year for ionisation, optical and beam types. Heads that have been cleaned but not re-certified post-cleaning will be flagged. Heads beyond their maker-rated 10-year service life (typical for Autronica, Consilium and Notifier marine) are condemned at Special, regardless of sensitivity readings.

Run the Solo 330 functional test on every head; capture the chamber reading from the maker's service tool; replace the heads scheduled for end-of-life regardless of operational status. We carry replacement heads for the major marine brands as ship's spare consumables — change-out is faster than re-certification of an end-of-life head, and the surveyor accepts the new ones without further dispute.

6. UPS battery discharge under load — the GMDSS test extended

The GMDSS reserve battery discharge test runs annually. The Special Survey extends the test to every UPS bank on the vessel — bridge navigation UPS, BWTS control UPS, fire panel UPS, IAS UPS, switchboard tripping coil UPS. Each has to deliver its rated capacity under maker-defined load for the documented autonomy time.

We run discharge banks calibrated against the load profile for each UPS. Vessels with UPS banks that have been topped up but never discharge-tested are common; the Special Survey is where 'looks charged' is replaced with 'measures full capacity for the rated time'. Replacement of failing banks before the survey is faster than after.

7. Earthing continuity audit — every JB lug torque-verified

Earth continuity from every junction box back to the hull-earth reference is the test surveyors run that nobody on board expects. A Megger DLRO10HD low-resistance ohmmeter measures the bonding path; readings above 100 milliohm on a 4mm² bonding strap indicate a corroded lug or a loose torque, and the surveyor will pick on it. The remedy is to retorque every accessible bonding lug against the maker spec and re-test.

We attend the audit with a torque wrench calibrated to the marine standard (typically 8–14 Nm on M6 brass lugs) and capture the readings to a class-witnessed log. The audit takes a day on a typical bulker, two days on a container vessel. It is the most preventable Special Survey finding category in our experience.

8. PMS load-share verification under transient load

The Power Management System (PMS) is checked at every Annual on paper; the Special Survey checks under load. A transient load — typically a bow thruster start or a heavy crane swing — should result in a load share of ±10% kW between running gensets within the maker-spec response time. Vessels with PMS that has been re-configured for fleet-specific operations sometimes fail this on the transient; the steady-state share is fine.

Capture the load share with a Hioki PW3198 power-quality analyser at the load-share CT outputs during a scheduled transient event. Compare against the maker's response curve. If the share is outside ±10% during the transient, the load-share CT installation or the PMS gain setting is the next investigation step.

9. Class report templates — DNV / BV / ABS / Lloyd's / TL formats

Each class society has a slightly different Special Survey report format. DNV uses the Form D series; BV uses the AS-1140; ABS uses the SR-12; Lloyd's uses the SP-100; Türk Loydu uses a single combined PDF. The technical content is the same; the format and the appendix ordering differs. We carry templates pre-formatted to each society to compress the post-attendance correspondence cycle.

The surveyor receives the completed package by email before they sign the certificate. Vessels that have the package ready before the surveyor leaves the gangway close their Special Survey in days rather than the weeks of back-and-forth that follow incomplete reporting.

10. When to schedule the survey relative to dry dock

The Special Survey window overlaps the dry-docking window by design — vessels save attendance days by combining the two. The trade-off is that the dry-dock work itself generates new electrical changes (motor refurbishments, switchboard cleaning, new lighting fixtures) that the surveyor then has to re-acceptance. The cleanest sequence is to schedule the major electrical work for the early dry-dock days, leave a settled-state buffer of 48 hours, then start the survey attendance.

We coordinate the survey window with the yard and the class surveyor at vessels with a planned dry-dock in the coming 12 months. Early coordination is the single biggest determinant of total survey time on board.

FAQ

How early should Special Survey preparation start?
Three months ahead for a routine bulker or tanker; six months ahead for a container vessel or offshore unit with extensive automation. The 10-point walk-through itself takes two to three working days; the remediation of any findings drives the rest of the timeline.
Which other surveys overlap with the 5-year Special?
The dry-dock attendance, the BWTS commissioning anniversary, the GMDSS annual radio survey, and the IOPP renewal if it falls in the same window. We coordinate the schedule so the surveyors witness overlapping items once instead of repeatedly.
Can we attend the survey itself on board, alongside the surveyor?
Yes — and this is the recommended setup for vessels with complex automation or HV installations. The ETO answers the surveyor's questions on the spot, runs the supporting tests in real time, and produces the class-acceptable report before the surveyor leaves.
Related service

Book a Special Survey electrical attendance

/services/switchboard

Related supply

Source ACB trip units and switchboard spares

/supply

Published by Levent Marine — Florida-based, Wyoming LLC — 24/7 worldwide